An air to air heat exchanger cools the air inside a cabinet without letting outside air in. Two fans and two separate air paths share one core: the internal loop stays closed, the external loop pulls ambient air across the other side of the core, and heat crosses the metal between them. Dust, oil mist and wash water stay on the outside.
The rating is in W/K, not in watts. Useful cooling is the specific thermal output multiplied by the temperature difference between the internal air and the ambient, minus what the enclosure wall already dissipates. A 45 W/K unit moves about 675 W at a 15 K difference and only about 225 W at 5 K. That is why the same unit looks adequate in a spring commissioning and fails in August, and why the calculation has to use the hottest week rather than the yearly average.
The working envelope is narrow and worth stating. The internal circuit is IP54 and the external circuit IP34, as the outside face has to pass air and therefore cannot be sealed. The ambient range is -5 to +55 C, the controller holds a set point shown on a digital display (default +35 C), and a floating fault contact reports an overtemperature. Where the internal air can drop below its own dew point the unit cannot dry the cabinet, so the set point has to stay above dew point or a heater has to hold the baseline.
Key Specifications
| Model | Specific thermal output | Air throughput 50 / 60 Hz | Rated current 230 V model | W x H x D | Weight |
|---|---|---|---|---|---|
| SK 3126 | 17.5 W/K | 265 / 315 m3/h external and internal | 0.11 / 0.13 A | 280 x 550 x 150 mm | 10 kg |
| SK 3127 | 30 W/K | 480 / 525 m3/h external and internal | 0.28 / 0.34 A | 400 x 950 x 205 mm | 18 kg |
| SK 3128 | 45 W/K | 600 / 625 m3/h external and internal | 0.30 / 0.40 A | 400 x 950 x 205 mm | 19 kg |
| SK 3129 | 60 W/K | 860 / 900 m3/h external and internal | 0.38 / 0.40 A | 400 x 950 x 225 mm | 21 kg |
| SK 3130 | 90 W/K | 850 / 945 m3/h external and internal | 0.65 / 0.90 A | 400 x 1580 x 215 mm | 34 kg |
Included Models and Order Codes
The 100 codes are 230 V and the 115 codes are 115 V, with the same core and the same footprint inside a size class. Fan power, air throughput and pre-fuse follow the table above; the 3130 class takes a 4 A pre-fuse and the smaller classes take 2 A.
| Part number | Specific output | Supply | Rated current 50 / 60 Hz | Air throughput 50 / 60 Hz | W x H x D | Weight |
|---|---|---|---|---|---|---|
| 3126.100 | 17.5 W/K | 230 V, 1~, 50/60 Hz | 0.11 / 0.13 A | 265 / 315 m3/h | 280 x 550 x 150 mm | 10 kg |
| 3126.115 | 17.5 W/K | 115 V, 1~, 50/60 Hz | 0.23 / 0.25 A | 265 / 315 m3/h | 280 x 550 x 150 mm | 10 kg |
| 3127.100 | 30 W/K | 230 V, 1~, 50/60 Hz | 0.28 / 0.34 A | 480 / 525 m3/h | 400 x 950 x 205 mm | 18 kg |
| 3127.115 | 30 W/K | 115 V, 1~, 50/60 Hz | 0.55 / 0.70 A | 480 / 525 m3/h | 400 x 950 x 205 mm | 18 kg |
| 3128.100 | 45 W/K | 230 V, 1~, 50/60 Hz | 0.30 / 0.40 A | 600 / 625 m3/h | 400 x 950 x 205 mm | 19 kg |
| 3128.115 | 45 W/K | 115 V, 1~, 50/60 Hz | 0.60 / 0.80 A | 600 / 625 m3/h | 400 x 950 x 205 mm | 19 kg |
| 3129.100 | 60 W/K | 230 V, 1~, 50/60 Hz | 0.38 / 0.40 A | 860 / 900 m3/h | 400 x 950 x 225 mm | 21 kg |
| 3129.115 | 60 W/K | 115 V, 1~, 50/60 Hz | 0.65 / 0.80 A | 860 / 900 m3/h | 400 x 950 x 225 mm | 21 kg |
| 3130.100 | 90 W/K | 230 V, 1~, 50/60 Hz | 0.65 / 0.90 A | 850 / 945 m3/h | 400 x 1580 x 215 mm | 34 kg |
| 3130.115 | 90 W/K | 115 V, 1~, 50/60 Hz | 1.30 / 1.80 A | 850 / 945 m3/h | 400 x 1580 x 215 mm | 34 kg |
Useful Cooling by Temperature Difference
The figures below are the specific output multiplied by the internal to ambient difference, before the wall contribution is subtracted. They are the number to compare with the internal heat load, and the reason a 17.5 W/K unit is not a 17.5 W unit.
| Difference inside to outside | 17.5 W/K | 45 W/K | 90 W/K |
|---|---|---|---|
| 5 K | 88 W | 225 W | 450 W |
| 10 K | 175 W | 450 W | 900 W |
| 15 K | 263 W | 675 W | 1350 W |
| 20 K | 350 W | 900 W | 1800 W |
Key Features
Two separate air paths – the internal loop never mixes with the external loop, so a dusty or oily site does not reach the electronics.
Rating in W/K – 17.5, 30, 45, 60 and 90 W/K in one family, so the unit is chosen by the heat load and the site temperature rather than by enclosure size.
Controller with digital display – set point shown and adjustable at the unit, default +35 C, with a floating fault contact for an overtemperature.
IP54 inside, IP34 outside – the internal face is protected against dust and splash, the external face passes air by definition.
Two supply voltages – 230 V and 115 V versions of every size, with the same core and the same cut-out inside a size class.
Filter mats as consumables – the external circuit takes a mat that is changed on the maintenance round, which is what keeps the W/K figure from drifting down over a year.
Applications
Heat exchangers are picked where the cabinet has to stay closed. Three patterns repeat.
Outdoor telecom and roadside cabinets – dust and insects outside, a sealed internal loop, and a heat load that rises with every added radio or power module.
Machine tools with oil mist – the coolant mist would clog a filter fan within weeks, while the heat exchanger core keeps the mist on the outside face.
Food and beverage wash-down areas – hose-down cleaning on the outside, a closed internal circuit, and a stainless or coated mounting frame.
Heat exchangers are quoted with the enclosure cut-out and the filter mats, and the SUPERB PCBA and the SUPERB PCB are checked against the same thermal calculation so the W/K figure covers the real heat load instead of the nameplate.
Sourcing and Cross-Reference
Start from the heat load and the worst ambient, not from the enclosure size. A 600 mm wide cabinet with 900 W of drives needs the 60 or 90 W/K class in a 40 C room, while the same cabinet with 300 W is served by the 30 W/K class.
Count the wall. A sheet steel enclosure dissipates roughly 5.5 W per square metre per kelvin, so a 2 m2 surface at 15 K removes about 165 W before any unit is fitted. Ignoring that figure oversizes the unit, ignoring the sun load undersizes it.
Leave the clearances the maker asks for: about 60 mm at the sides and 100 mm below the unit, so the external air can enter and leave. A unit mounted tight into a cable duct runs at half its rating.
Plan the filter mat change. The mat is the only part that wears, and a mat loaded with dust turns a 45 W/K unit into a 25 W/K unit without any fault appearing. See lead time and availability for units quoted with a year of mats.
The SUPERB Assembly team fits the unit with the internal fan clear of the wiring duct, because a heat exchanger blowing across a duct heats the air it has just cooled.
Q: Will a heat exchanger hold 35 C inside when the outside air reaches 45 C?
A: Yes. Send the internal heat load, the highest summer ambient and the enclosure size; the SUPERB Tech team returns the W/K class that holds the internal temperature.
Why Builders Buy Heat Exchangers From SUPERB
- Sized in W/K against the load: the class is chosen from the heat load and the summer ambient, not from the enclosure width.
- Sealed internal circuit: IP54 inside and IP34 outside is stated per unit, so a dusty site is quoted the right part.
- Both supply voltages: 230 V and 115 V versions of every size, which matters on exported panels.
- Cut-out and mats quoted together: the drilling template, the filter mats and the fault contact are part of the same quote.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Filter Fan Units and Exhaust Filters, Enclosure Air Conditioners, Enclosure Panel Heaters and Thermostats, Enclosure Hygrostats and Humidity Controllers, Component Lead Time Solutions.