Enclosure Panel Heaters and Thermostats for Cold Cabinets
Product Specifications
Product Overview
A cabinet that is switched off overnight cools faster than the air around it. When the inside surface drops below the dew point, moisture condenses on the board, and the first power up in the morning finds a wet circuit. The damage is not the water itself but the corrosion and the tracking that follow.
A panel heater keeps the inside surface above the dew point. The parts here are PTC heaters, which means the element raises its resistance as it warms and settles at a self limiting temperature instead of running open loop. That is why the same heater can be rated 8 to 10 W at one ambient and 27 to 34 W under another: the output is a curve, not a fixed number.
Two families cover the range. Heaters without a fan run from 10 W to 150 W and rely on convection inside a small cabinet. Heaters with a built in fan run from 235 W to 870 W and move the air so the heat reaches the far corner of a large enclosure. A 2 m tall cabinet with a single 50 W heater gets a warm patch at the bottom and a cold corner at the top.
Control is a separate order. The heater has no set point, so a thermostat, a hygrostat or a digital controller decides when it runs. The usual arrangement is a thermostat set a few degrees above the lowest expected ambient, or a hygrostat set at 65 percent relative humidity, which reacts to the condition that actually causes the condensation.
Key Specifications
| Parameter | Heaters without fan | Heaters with fan |
|---|---|---|
| Heating technology | PTC element, self regulating | PTC element with axial fan |
| Thermal output | 8 to 150 W continuous, seven models | 235 to 870 W continuous, six models |
| Rated voltage | 110 to 240 V, 1 phase, 50/60 Hz | 115 V or 230 V, 1 phase, 50/60 Hz |
| Pre fuse | 2 A or 4 A depending on model | 4 A, 6 A or 10 A depending on model |
| Housing sizes | 120 x 45 x 46 mm up to 180 x 90 x 75 mm | 200 x 103 x 103 mm on all six models |
| Terminals | Quick connection terminals, double on the larger models | Quick connection terminals |
| Mounting | Screwed to the cabinet plate, bottom adapter available | Screwed to the cabinet plate, bottom adapter available |
| Approvals | UR, cUR, CSA | UR, cUR, CSA |
| Ambient limit | Rated at 10 C ambient, output falls as the ambient rises | Rated at 10 C ambient, fan rated for continuous duty |
| Control | External thermostat, hygrostat or digital controller | External thermostat, hygrostat or digital controller |
| Accessories | 3110.000 thermostat, 3118.000 hygrostat, 3114.200 digital, 3110.200 adapter | Same accessory set as the fan free models |
Included Models and Order Codes
The output of a PTC heater is quoted as a pair, because the element limits itself and the figure depends on the ambient it is working in. The first number is the low end and the second is the high end at the stated condition. Sizes are the housing, not the heated volume, and the pre fuse is the value the cabinet builder has to provide on the supply.
| Model | Type | Output (W) | Voltage | H x W x D (mm) | Pre fuse |
|---|---|---|---|---|---|
| 3105.310 | Heater, no fan | 8 to 10 | 110 to 240 V | 120 x 45 x 46 | 2 A |
| 3105.320 | Heater, no fan | 18 to 20 | 110 to 240 V | 120 x 45 x 46 | 2 A |
| 3105.330 | Heater, no fan | 23 to 30 | 110 to 240 V | 155 x 64 x 56 | 4 A |
| 3105.340 | Heater, no fan | 49 to 50 | 110 to 240 V | 155 x 64 x 56 | 4 A |
| 3105.350 | Heater, no fan | 63 to 75 | 110 to 240 V | 230 x 64 x 56 | 4 A |
| 3105.360 | Heater, no fan | 86 to 100 | 110 to 240 V | 165 x 90 x 75 | 4 A |
| 3105.370 | Heater, no fan | 130 to 150 | 110 to 240 V | 180 x 90 x 75 | 4 A |
| 3105.410 | Heater with fan | 235 to 250 | 115 V | 200 x 103 x 103 | 4 A |
| 3105.380 | Heater with fan | 250 to 265 | 230 V | 200 x 103 x 103 | 4 A |
| 3105.420 | Heater with fan | 355 to 400 | 115 V | 200 x 103 x 103 | 6 A |
| 3105.390 | Heater with fan | 400 to 415 | 230 V | 200 x 103 x 103 | 6 A |
| 3105.430 | Heater with fan | 710 to 800 | 115 V | 200 x 103 x 103 | 10 A |
| 3105.4000 | Heater with fan | 800 to 870 | 230 V | 200 x 103 x 103 | 6 A |
Thermostats, Hygrostats and Mounting Accessories
The heater has no set point, so the control is a separate line on the order. The thermostat switches on temperature, the hygrostat switches on relative humidity, and the digital controller does both with a display. All three fit the same mounting rail, and the bottom adapter moves a heater to the lower plate of a cabinet where the cold air sits.
| Part Number | Item | Function | Range or rating | Fits |
|---|---|---|---|---|
| 3110.000 | Enclosure thermostat | Switches a heater, fan or heat exchanger on temperature | 5 C to 60 C set point, 10 A at 250 V AC | All heaters in the range |
| 3118.000 | Hygrostat | Switches on relative humidity | Set point around 65 percent RH | All heaters in the range |
| 3114.200 | Digital controller | Temperature display and switching in one unit | Digital set point with display | All heaters in the range |
| 3110.200 | Bottom mounted adapter | Moves the heater to the base plate | Mechanical part | 3105.310 to 3105.370 |
Key Features
PTC element, self limiting – The heater raises its resistance as it warms, so a blocked airflow does not turn it into a hot spot with no limit.
Output quoted at two ambients – The pair of numbers on the sheet is the honest figure, because a 150 W heater at 10 C is not a 150 W heater at 40 C.
Seven sizes without a fan – From 10 W to 150 W in housings that fit a small wall mounted cabinet or a roadside kiosk.
Six sizes with a fan – 235 W to 870 W in one 200 mm housing, for a large cabinet where convection alone leaves a cold corner.
Quick connection terminals – Double terminals on the larger models let the heater be looped with the next one on the same supply.
Separate control – Thermostat, hygrostat and digital controller are ordered to the site condition, not fixed inside the heater.
CSA and UR approvals – The range carries UR, cUR and CSA, which is what a North American panel shop asks for before the cabinet is released.
Bottom adapter – The heater can be moved to the cold lower plate, where the air that needs warming actually sits.
Applications
A heater is specified where the cabinet is colder than the air around it, or where the air inside is humid. The four cases below cover most of the orders.
Outdoor cabinets and kiosks – A 50 W heater on a thermostat keeps a roadside cabinet above the dew point through a cold night and stops condensation on the modem board.
Telecom and remote radio sites – A fan heater in a 2 m cabinet moves the heat to the top, where the radio unit sits and where convection alone leaves the coldest surface.
Food and pharma washdown areas – A sealed cabinet in a chilled room needs a heater on a hygrostat, because the humidity outside the cabinet is the condition that drives the condensation.
Cold stores and unheated warehouses – A 10 W heater in a small junction box is enough to keep the terminals dry when the store runs at 2 C and the box is opened twice a day.
A heater is chosen against the coldest night the cabinet will see, and the SUPERB PCB panel drawing carries the surface area, the ambient and the thermostat set point so the sizing can be checked. On the SUPERB PCBA build the heater and the thermostat are wired on the plate and the set point is tested before the door goes on.
Sourcing and Cross-Reference
The heater is the easy part of the order. The hard part is the control and the sizing, because a heater that is too small runs continuously and a heater that is too large cycles and cooks the air near it. The starting figure is the cabinet surface area, the lowest ambient and the temperature the electronics need, and the heater is then chosen from the curve rather than from the wattage alone.
An enclosure with a fan heater needs the fan to run whenever the heater runs, and a cabinet with a filter fan needs the heater to be off when the fan is on. That interlock is a wiring decision, and the thermostat with a changeover contact is what makes it possible without adding a relay.
The accessories are ordered with the heater, because a heater without a thermostat has no set point and will run whenever the supply is on. The bottom adapter is a small part that decides whether the heat starts at the cold plate or at the top of the cabinet, and it is worth adding to the same line.
SUPERB Assembly mounts the heater low in the cabinet, keeps 100 mm clear above it for convection and wires the thermostat in series with the supply, because a heater on a permanent supply is a fire risk once the door is closed.
Q: Can you supply a 3105.350 heater with a 3110.000 thermostat and the bottom adapter, wired for 230 V, for a roadside cabinet that drops to -15 C?
A: Send the cabinet size, the lowest ambient, the internal target temperature and the supply voltage. The SUPERB Tech desk replies with the heater, the control and the pre fuse, and states the output at your ambient rather than the headline figure.
Why Buy Panel Heaters Through SUPERB
- Output read from the curve: The two figures on the datasheet are used for sizing, so the heater is chosen against the site ambient rather than the headline wattage.
- Control quoted with the heater: Thermostat, hygrostat or digital controller is added on the same line, because the heater alone has no set point.
- Fan and no fan from one range: Small cabinets take the 10 W to 150 W models and large ones take the 235 W to 870 W models, from the same supplier.
- Approvals checked: UR, cUR and CSA are confirmed on the model that is quoted, which matters when the cabinet is exported to North America.
- Panel build support: The assembly team mounts the heater, the thermostat and the interlock wiring on the plate and tests the set point before the cabinet ships.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DC Axial Fans for Enclosure Cooling, Fan Guards and Filter Screens for Enclosure Cooling, Breather Vents and Pressure Equalization Plugs, Thermal Fuses and Temperature Cutoffs, Screw Terminal Blocks and Pluggable Connectors, Component Lead Time Solutions.