Contact Us
  • Home
  • COMPONENTS
  • Filter Fan Units and Exhaust Filters for Enclosure Cooling

Filter Fan Units and Exhaust Filters for Enclosure Cooling

Fan-and-filter units from 20 to 770 m3/h in seven cut-out sizes. Installed airflow drops 10 to 25 percent once the outlet filter and mat are fitted. IP54 standard, IP55 with a fine mat, IP56 with a hose-proof hood. Pfannenberg and Rittal units quoted with outlet filters and spare mats.
quote now

Product Specifications

Product Overview

A fan-and-filter unit is the cheapest way to keep a cabinet near ambient: it pulls outside air through a mat, and an exhaust filter on the opposite wall lets the air out. The airflow printed on the unit is the unimpeded figure; once an outlet filter and mat are fitted, 10 to 25 percent of it goes away.

Two mounting standards dominate. Rittal TopTherm units use cut-outs from 92 x 92 mm to 292 x 292 mm with airflow from 20 to 770 m3/h. Pfannenberg 4th generation units use 125 x 125 mm and 223 x 223 mm cut-outs and stay compatible with the older installation sizes.

Sizing starts from heat load, not from the biggest fan. A 100 m3/h unit at a 10 K difference removes about 330 W, so a 1 kW cabinet needs either 300 m3/h or a larger allowed difference.

Key Specifications

UnitAirflow 50/60 HzCut-out W x HSupplyCurrent 50/60 HzPowerNoiseProtection
Rittal SK 3237.10020 / 25 m3/h92 x 92 mm230 V AC0.065 / 0.052 A11 / 9 W38 / 43 dB(A)IP54
Rittal SK 3238.10055 / 66 m3/h124 x 124 mm230 V AC0.12 / 0.11 A19 / 17 W46 / 49 dB(A)IP54
Rittal SK 3239.100105 / 120 m3/h177 x 177 mm230 V AC0.12 / 0.11 A19 / 17 W46 / 49 dB(A)IP54
Rittal SK 3240.100180 / 160 m3/h224 x 224 mm230 V AC0.19 / 0.18 A33 / 33 W51 / 46 dB(A)IP54
Rittal SK 3241.100230 / 250 m3/h224 x 224 mm230 V AC0.27 / 0.28 A42 / 46 W54 / 56 dB(A)IP54
Rittal SK 3243.100550 / 600 m3/h292 x 292 mm230 V AC0.37 / 0.48 A71 / 89 W59 / 61 dB(A)IP54
Rittal SK 3244.100700 / 770 m3/h292 x 292 mm230 V AC0.75 / 0.80 A70 / 80 W65 / 68 dB(A)IP54
Pfannenberg PF 22.00061 / 70 m3/h125 x 125 mm230 V AC0.12 / 0.18 A19 / 18 W44 dB(A)IP54, IP55 version
Pfannenberg PF 43.000223 / 247 m3/h223 x 223 mm230 V AC0.16 / 0.14 A49 / 42 W53 dB(A)IP54, IP55 version

Included Models and Order Codes

Voltage variants share one cut-out, so the same cabinet drawing serves a 230 V, a 115 V and a 24 V DC build. Spring terminals take the supply without a screwdriver.

Part numberSupplyCut-outAirflow 50/60 HzNotes
SK 3237.100 / 3237.110 / 3237.124230 V / 115 V / 24 V DC92 x 92 mm20 / 25 m3/hEMC version 3237.600
SK 3238.100 / 3238.110 / 3238.124230 V / 115 V / 24 V DC124 x 124 mm55 / 66 m3/hEMC version 3238.600
SK 3239.100 / 3239.110 / 3239.124230 V / 115 V / 24 V DC177 x 177 mm105 / 120 m3/hEMC version 3239.600
SK 3240.100 / 3240.110 / 3240.124230 V / 115 V / 24 V DC224 x 224 mm180 / 160 m3/hEMC version 3240.600
SK 3241.100 / 3241.110 / 3241.124230 V / 115 V / 24 V DC224 x 224 mm230 / 250 m3/hEMC version 3241.600
SK 3243.100 / 3243.110230 V / 115 V292 x 292 mm550 / 600 m3/hEMC version 3243.600
SK 3244.100 / 3244.110 / 3244.140230 V / 115 V / 400 V 3 phase292 x 292 mm700 / 770 m3/hEMC version 3244.600
PF 22.000 11622101055230 V AC, IP54125 x 125 mm61 / 70 m3/h115 V 11622151055, 24 V DC 11622801055
PF 22.000 11622103055230 V AC, IP55125 x 125 mm56 / 64 m3/hFluted filter mat
PF 43.000 11643101055230 V AC, IP54223 x 223 mm223 / 247 m3/h115 V 11643151055, 24 V DC 11643801055
PF 43.000 11643103055230 V AC, IP55223 x 223 mm233 / 265 m3/hFluted filter mat

Outlet Filters and Filter Mats

An outlet filter is not optional: without it the air has nowhere to leave and the cabinet pressurises. The airflow column below is the figure measured with the filter and standard mat in place.

Part numberFor unitAirflow with filterFilter classNotes
Rittal SK 3237.200SK 3237 series15 / 18 m3/hG2 mat 3321.700One outlet filter
Rittal SK 3238.200SK 3238 series43 / 50 m3/h, 46 / 56 m3/h with twoG2 mat 3322.700One or two filters
Rittal SK 3239.200SK 3239 series87 / 100 m3/h, 93 / 108 m3/h with twoG3 mat 3171.100Fine mat 3181.100 gives IP55
Rittal SK 3240.200SK 3240 and 3241138 / 121 m3/h on SK 3240.100G3 mat 3172.100Fine mat 3182.100
Rittal SK 3243.200SK 3243 and 3244465 / 510 m3/h on SK 3243.100G3 mat 3173.100Fine mat 3183.100
Pfannenberg PFA 20.000 11720001055PF 22.00044 m3/h with filter gridG4 mat 186116000305 mats per pack
Pfannenberg PFA 40.000 11740001055PF 43.000201 / 223 m3/hG4 mat 1861160003224 piece packing 11740001412

Key Features

Airflow drops when the filter goes on – the unimpeded figure is not the installed figure, so size on the filtered number, not the catalogue headline.

Cut-out compatibility across generations – Pfannenberg size 2 and size 4 units drop into the older 125 x 125 mm and 223 x 223 mm openings.

IP54 to IP56 by accessory – standard mat gives IP54, a fine filter mat IP55, and a hose-proof hood IP56.

Filter class follows the mat – G2 and G3 chopped-fibre mats for dust, F5 fine mats where the air has to be cleaner.

Tool-free service – the louvred grille unclips for a mat change, and the fan module lifts out without removing the frame.

EMC versions for drives cabinets – 323x.600 and 324x.600 units use the same cut-outs with a screened frame.

Applications

Cabinet cooling is bought with the enclosure, not after it. Three patterns repeat.

Automation and drive cabinets – inverter and servo cabinets where the heat load is steady and the ambient air is filtered.

Telecom and RF outdoor cabinets – hose-proof hoods and fine mats for dusty or wet sites.

Medical and laboratory analysers – low-noise units with cleanable mats where the analyser sits beside the operator.

On cabinet projects the fan unit, outlet filter and thermostat arrive as one line item, and the SUPERB PCBA and the SUPERB PCB are checked against the same cut-out drawing.

Sourcing and Cross-Reference

Heat load and allowed difference decide the size: multiply the airflow in m3/h by 0.33 and by the temperature difference in kelvin to get watts.

Ask for the cut-out drawing early. A 224 x 224 mm opening will not take a 177 x 177 mm unit, and the two differ by 75 m3/h.

Filter mats are consumables. Quote them with the unit and allow one spare pack per year of service.

Older fan units are often obsolete while the cut-out is still good. Lead time and availability covers the drop-in replacements that fit the same opening.

When the SUPERB Assembly team builds the panel, the unit is fitted at the cut-out before the harness is dressed, so the mat can still be changed from outside.

Q: Can you match an existing cut-out when the original fan unit is discontinued?

A: Yes. Send the cut-out size and a photo of the old unit; the SUPERB Tech team quotes the current unit that fits the same opening, with the outlet filter and mat.

Why Builders Buy Filter Fan Units From SUPERB

  1. Sized on the filtered airflow: the quote states the airflow with the outlet filter and mat, not the headline figure.
  2. Cut-out matched to the old unit: the replacement is picked by opening size, so no sheet metal work is needed.
  3. Outlet filter and mat in the same quote: one line item covers the unit, the exhaust filter and a spare mat pack.
  4. Voltage variants for export builds: 230 V, 115 V and 24 V DC versions share the same cut-out and the same drawing.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: DC Axial Fans for Enclosure Cooling, Enclosure Panel Heaters and Thermostats, Cable Entry Plates and Brush Grommets, Component Lead Time Solutions.