Shunt Trip and Undervoltage Release Coils

Trip coils that open a DIN rail breaker from a control signal, fitted to the side of the device in one or two modules. Shunt trips work on an applied voltage; undervoltage releases hold the breaker closed and drop it when the coil loses supply. Coil voltages run from 12 V DC up to 415 V AC, with 110 to 240 V AC as the common panel control values. The two functions are not interchangeable, and the trip window of an undervoltage release decides whether it suits an emergency off loop.
quote now

Product Specifications

Product Overview

A miniature circuit breaker protects a circuit but has no way to be opened from a distance. A trip coil adds that: a small solenoid sits beside the breaker, and when the control circuit energises it, a plunger releases the breaker mechanism. The same body can also be used for a local emergency stop, a fire panel signal or a PLC command, which is why the coil is one of the most frequently added accessories on a panel.

There are two families and they behave in opposite ways. A shunt trip opens the breaker when voltage is applied, and the coil is short time rated: the internal contact opens as soon as the breaker trips, so the coil does not stay energised. An undervoltage release is energised continuously while the breaker is closed, and it trips when the supply falls below its window, typically between 70 and 35 percent of rated voltage. That second behaviour is what makes it useful in an emergency off loop: pressing the button removes the coil supply and the breaker cannot be closed again until the voltage is restored.

Choosing between them comes down to one question. If the safe state is reached by a signal, use a shunt trip. If the safe state has to be reached when the supply disappears, or if the breaker must be prevented from being closed while a guard is open, use an undervoltage release. Getting this backwards is the most common ordering error, because both parts look like a coil in a module and both fit the same slot.

Key Specifications

FamilyFunctionCoil voltageBehaviourWidthNote
Schneider iMX A9A26476shunt trip100 to 415 V AC, 110 to 130 V DCtrips when energised2 modules, 18 mmshort time coil, internal cut-off
Schneider iMX A9A26477shunt trip48 V AC or DCtrips when energised2 modules, 18 mmsame body, 48 V control
Schneider iMX A9A26478shunt trip12 to 24 V AC or DCtrips when energised2 modules, 18 mmPLC output can drive it
Schneider iMN A9A26500undervoltage release220 to 240 V ACtrips between 70 and 35 percent Un2 modules, 18 mmprevents reclosing until restored
Schneider iMNsdelayed undervoltage24 to 240 V ACtrips after an adjustable delay2 modules, 18 mmrides through a short dip
Schneider iMNxindependent undervoltage220 to 240 V AC, 380 to 415 V ACtrips below the window2 modules, 18 mmnot tied to the monitored voltage
ABB S2C-A1shunt trip12 to 60 V AC or DCtrips when energised1 modulerelease under 10 ms
ABB S2C-A2shunt trip110 to 415 V AC, 110 to 250 V DCtrips when energised1 modulecoil 225 ohm, 2.7 A at 415 V
ABB S2C-UA230ACundervoltage release230 V ACtrips at 0.35 to 0.7 Un1 module3.7 VA holding
Siemens 5ST3030shunt trip110 to 415 V ACtrips when energised1 moduleoperating range 0.7 to 1.1 Un
Siemens 5ST3031shunt trip24 to 48 V AC or DCtrips when energised1 modulelow voltage control
Siemens 5ST3040undervoltage release230 V ACtrips when the coil drops1 moduleemergency off loop

Included Models and Order Codes

The order code on a trip coil is the voltage, and nothing else. On Schneider the iMX family is the shunt trip and the iMN family is the undervoltage release, with the suffix s for delayed and x for independent of the supply; the number after the family is the coil voltage group. On ABB the last characters of S2C-UA name the voltage and the current type, so S2C-UA230AC and S2C-UA230DC are two different parts that fit the same breaker.

Part numberFamilyFunctionCoil voltageConsumptionFitsNote
A9A26476Schneider iMXshunt trip100 to 415 V AC, 110 to 130 V DCon requestiC60, iID, iDPN Vigi2 modules
A9A26477Schneider iMXshunt trip48 V AC or DCon requestiC60, iID, iDPN Vigi2 modules
A9A26478Schneider iMXshunt trip12 to 24 V AC or DCon requestiC60, iID, iDPN Vigi2 modules
A9A26500Schneider iMNundervoltage release220 to 240 V ACon requestiC60, iID, iDPN Vigitrip 70 to 35 percent
A9A26946Schneider iMX+OFshunt trip with contact100 to 415 V ACon requestiC60, iIDone NO or NC status contact
S2C-A1ABB S2Cshunt trip12 to 60 V AC or DC2.2 to 14 A at 12 to 60 VS200, DS200, SD200under 10 ms release
S2C-A2ABB S2Cshunt trip110 to 415 V AC, 110 to 250 V DC0.35 to 2.7 AS200, DS200, SD200minimum release 77 V
S2C-UA24DCABB S2C-UAundervoltage release24 V DC2 VAS200, DS200, SD200trip 0.35 to 0.7 Un
S2C-UA110ACABB S2C-UAundervoltage release110 V AC3.5 VAS200, DS200, SD200trip 0.35 to 0.7 Un
S2C-UA230ACABB S2C-UAundervoltage release230 V AC3.7 VAS200, DS200, SD200trip 0.35 to 0.7 Un
S2C-UA400ACABB S2C-UAundervoltage release400 V AC2.4 VAS200, DS200, SD200for 400 V control
5ST3030Siemens 5ST3shunt trip110 to 415 V ACon request5SL, 5SY, 5SP0.7 to 1.1 Un
5ST3031Siemens 5ST3shunt trip24 to 48 V AC or DCon request5SL, 5SY, 5SP0.9 to 1.15 Un
5ST3040Siemens 5ST3undervoltage release230 V ACon request5SL, 5SY, 5SP0.85 to 1.1 Un
5ST3041Siemens 5ST3undervoltage release110 V DCon request5SL, 5SY, 5SPrailway and DC control
5ST3042Siemens 5ST3undervoltage release24 V DCon request5SL, 5SY, 5SPPLC rail control

Shunt Trip or Undervoltage Release

The two functions answer different questions, and a panel sometimes needs both on the same breaker. The table sets out what each one does when the control supply is healthy, when a button is pressed and when the supply itself fails.

ConditionShunt trip (MX)Undervoltage release (MN)Consequence for the panel
Control supply healthy, breaker closedcoil de-energised, no currentcoil energised continuouslyan undervoltage release draws holding power all day
Button or PLC contact closescoil energised, breaker opensnot affectedshunt trip needs a maintained pulse of a few hundred ms
Control supply failsbreaker stays closedbreaker opensonly the undervoltage release fails safe
Supply restored after a tripbreaker can be closed at oncebreaker cannot close until the coil is at voltagethe release gives a positive safety interlock
Guarded area openno effect unless wired to a switchcoil circuit opened, breaker held openthe release is the simpler interlock

Key Features

Two functions, one mounting slot – the shunt trip and the undervoltage release of the same family share the side pocket and the same width, so a change of concept does not change the enclosure.

Coil voltages from 12 V to 415 V – a PLC output at 24 V DC and a 400 V control circuit are both served inside the same family, without an interposing relay.

Trip window stated on the release – the 0.35 to 0.7 Un band is written per family, because a release that holds at 60 percent of nominal is not protecting the load.

Short time coil that cuts itself off – the shunt trip contact opens after the trip, so the coil does not burn if the control signal stays on, which is why no timer is needed in the circuit.

Status contact versions – the iMX+OF and the ABB auxiliary blocks add one changeover contact, so the PLC sees the breaker position rather than assuming the command worked.

Fits the breaker it is ordered with – each row names the breaker families it mounts on, so a coil is not bought for the wrong frame width.

Applications

These three uses explain most orders, and each one sets a different requirement on the coil.

Emergency off and fire panel trip – a shunt trip driven by the emergency circuit or the fire panel, opening the incoming breaker without anyone reaching the panel door.

Guarded machine interlock – an undervoltage release held closed by the guard circuit, so the drive cannot be re-energised while the guard is open and the breaker drops if the circuit is broken.

Remote load disconnection – a PLC output through a shunt trip on a feeder that has to be shed at night, with the status contact returning the breaker position to the controller.

The trip circuit is quoted with the board that drives it, so the SUPERB PCBA and the SUPERB PCB are checked against the same panel list and the output contact rating agrees with the coil current.

Sourcing and Cross-Reference

Write the coil voltage down before the brand. A 230 V AC coil on a 24 V DC control rail is a dead part on arrival, and the mistake is easy to make because the same family is sold at four voltages with one character of difference in the code. If the panel has both rails, decide which one the trip circuit belongs to and keep it there.

Decide whether the circuit must fail safe. A shunt trip does nothing when the control supply is lost, so a machine that must open on power failure needs an undervoltage release, or the shunt trip has to sit on a circuit that is itself supervised. In an emergency off loop the release is usually the cheaper and clearer answer.

Check the continuous consumption on the release. An undervoltage release holds 2 to 4 VA per breaker for as long as the panel is live, and a row of twenty of them is a real load on a small control transformer. The same calculation decides the transformer size, so see the control transformers page, and lead time and availability when the type is on allocation.

The SUPERB Assembly team runs the release coil on its own pair back to the guard circuit, because a release sharing a terminal with a signal lamp is the usual reason a machine will not reset.

Q: Can you supply the trip coils already fitted to the breakers, so the panel arrives with the accessory in place?

A: Yes. Send the breaker family, the control voltage and whether the circuit has to fail safe, and the SUPERB Tech team returns the coil, the width and the status contact that fit.

Why Panel Builders Buy Trip Coils From SUPERB

  1. Function named per row: shunt trip and undervoltage release are never mixed in one list, because the safe state of the panel depends on which one is fitted.
  2. Coil voltage explicit: the voltage and the current type are written out, so a 230 V AC and a 230 V DC part are not confused at the order stage.
  3. Compatibility listed: each row names the breaker families it mounts on, which avoids a coil that fits the slot but not the frame width.
  4. Trip window given: the percent band of the release is stated, so it can be checked against the emergency off requirement before the order is placed.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Residual Current Devices for Panel Feeders, Motor Protection Circuit Breakers for Panel Feeders, Control Transformers for Panel Control Voltage, Phase Failure and Voltage Monitoring Relays, Surge Protective Devices for AC Distribution Boards.