Shunt Trip and Undervoltage Release Coils
Product Specifications
Product Overview
A miniature circuit breaker protects a circuit but has no way to be opened from a distance. A trip coil adds that: a small solenoid sits beside the breaker, and when the control circuit energises it, a plunger releases the breaker mechanism. The same body can also be used for a local emergency stop, a fire panel signal or a PLC command, which is why the coil is one of the most frequently added accessories on a panel.
There are two families and they behave in opposite ways. A shunt trip opens the breaker when voltage is applied, and the coil is short time rated: the internal contact opens as soon as the breaker trips, so the coil does not stay energised. An undervoltage release is energised continuously while the breaker is closed, and it trips when the supply falls below its window, typically between 70 and 35 percent of rated voltage. That second behaviour is what makes it useful in an emergency off loop: pressing the button removes the coil supply and the breaker cannot be closed again until the voltage is restored.
Choosing between them comes down to one question. If the safe state is reached by a signal, use a shunt trip. If the safe state has to be reached when the supply disappears, or if the breaker must be prevented from being closed while a guard is open, use an undervoltage release. Getting this backwards is the most common ordering error, because both parts look like a coil in a module and both fit the same slot.
Key Specifications
| Family | Function | Coil voltage | Behaviour | Width | Note |
|---|---|---|---|---|---|
| Schneider iMX A9A26476 | shunt trip | 100 to 415 V AC, 110 to 130 V DC | trips when energised | 2 modules, 18 mm | short time coil, internal cut-off |
| Schneider iMX A9A26477 | shunt trip | 48 V AC or DC | trips when energised | 2 modules, 18 mm | same body, 48 V control |
| Schneider iMX A9A26478 | shunt trip | 12 to 24 V AC or DC | trips when energised | 2 modules, 18 mm | PLC output can drive it |
| Schneider iMN A9A26500 | undervoltage release | 220 to 240 V AC | trips between 70 and 35 percent Un | 2 modules, 18 mm | prevents reclosing until restored |
| Schneider iMNs | delayed undervoltage | 24 to 240 V AC | trips after an adjustable delay | 2 modules, 18 mm | rides through a short dip |
| Schneider iMNx | independent undervoltage | 220 to 240 V AC, 380 to 415 V AC | trips below the window | 2 modules, 18 mm | not tied to the monitored voltage |
| ABB S2C-A1 | shunt trip | 12 to 60 V AC or DC | trips when energised | 1 module | release under 10 ms |
| ABB S2C-A2 | shunt trip | 110 to 415 V AC, 110 to 250 V DC | trips when energised | 1 module | coil 225 ohm, 2.7 A at 415 V |
| ABB S2C-UA230AC | undervoltage release | 230 V AC | trips at 0.35 to 0.7 Un | 1 module | 3.7 VA holding |
| Siemens 5ST3030 | shunt trip | 110 to 415 V AC | trips when energised | 1 module | operating range 0.7 to 1.1 Un |
| Siemens 5ST3031 | shunt trip | 24 to 48 V AC or DC | trips when energised | 1 module | low voltage control |
| Siemens 5ST3040 | undervoltage release | 230 V AC | trips when the coil drops | 1 module | emergency off loop |
Included Models and Order Codes
The order code on a trip coil is the voltage, and nothing else. On Schneider the iMX family is the shunt trip and the iMN family is the undervoltage release, with the suffix s for delayed and x for independent of the supply; the number after the family is the coil voltage group. On ABB the last characters of S2C-UA name the voltage and the current type, so S2C-UA230AC and S2C-UA230DC are two different parts that fit the same breaker.
| Part number | Family | Function | Coil voltage | Consumption | Fits | Note |
|---|---|---|---|---|---|---|
| A9A26476 | Schneider iMX | shunt trip | 100 to 415 V AC, 110 to 130 V DC | on request | iC60, iID, iDPN Vigi | 2 modules |
| A9A26477 | Schneider iMX | shunt trip | 48 V AC or DC | on request | iC60, iID, iDPN Vigi | 2 modules |
| A9A26478 | Schneider iMX | shunt trip | 12 to 24 V AC or DC | on request | iC60, iID, iDPN Vigi | 2 modules |
| A9A26500 | Schneider iMN | undervoltage release | 220 to 240 V AC | on request | iC60, iID, iDPN Vigi | trip 70 to 35 percent |
| A9A26946 | Schneider iMX+OF | shunt trip with contact | 100 to 415 V AC | on request | iC60, iID | one NO or NC status contact |
| S2C-A1 | ABB S2C | shunt trip | 12 to 60 V AC or DC | 2.2 to 14 A at 12 to 60 V | S200, DS200, SD200 | under 10 ms release |
| S2C-A2 | ABB S2C | shunt trip | 110 to 415 V AC, 110 to 250 V DC | 0.35 to 2.7 A | S200, DS200, SD200 | minimum release 77 V |
| S2C-UA24DC | ABB S2C-UA | undervoltage release | 24 V DC | 2 VA | S200, DS200, SD200 | trip 0.35 to 0.7 Un |
| S2C-UA110AC | ABB S2C-UA | undervoltage release | 110 V AC | 3.5 VA | S200, DS200, SD200 | trip 0.35 to 0.7 Un |
| S2C-UA230AC | ABB S2C-UA | undervoltage release | 230 V AC | 3.7 VA | S200, DS200, SD200 | trip 0.35 to 0.7 Un |
| S2C-UA400AC | ABB S2C-UA | undervoltage release | 400 V AC | 2.4 VA | S200, DS200, SD200 | for 400 V control |
| 5ST3030 | Siemens 5ST3 | shunt trip | 110 to 415 V AC | on request | 5SL, 5SY, 5SP | 0.7 to 1.1 Un |
| 5ST3031 | Siemens 5ST3 | shunt trip | 24 to 48 V AC or DC | on request | 5SL, 5SY, 5SP | 0.9 to 1.15 Un |
| 5ST3040 | Siemens 5ST3 | undervoltage release | 230 V AC | on request | 5SL, 5SY, 5SP | 0.85 to 1.1 Un |
| 5ST3041 | Siemens 5ST3 | undervoltage release | 110 V DC | on request | 5SL, 5SY, 5SP | railway and DC control |
| 5ST3042 | Siemens 5ST3 | undervoltage release | 24 V DC | on request | 5SL, 5SY, 5SP | PLC rail control |
Shunt Trip or Undervoltage Release
The two functions answer different questions, and a panel sometimes needs both on the same breaker. The table sets out what each one does when the control supply is healthy, when a button is pressed and when the supply itself fails.
| Condition | Shunt trip (MX) | Undervoltage release (MN) | Consequence for the panel |
|---|---|---|---|
| Control supply healthy, breaker closed | coil de-energised, no current | coil energised continuously | an undervoltage release draws holding power all day |
| Button or PLC contact closes | coil energised, breaker opens | not affected | shunt trip needs a maintained pulse of a few hundred ms |
| Control supply fails | breaker stays closed | breaker opens | only the undervoltage release fails safe |
| Supply restored after a trip | breaker can be closed at once | breaker cannot close until the coil is at voltage | the release gives a positive safety interlock |
| Guarded area open | no effect unless wired to a switch | coil circuit opened, breaker held open | the release is the simpler interlock |
Key Features
Two functions, one mounting slot – the shunt trip and the undervoltage release of the same family share the side pocket and the same width, so a change of concept does not change the enclosure.
Coil voltages from 12 V to 415 V – a PLC output at 24 V DC and a 400 V control circuit are both served inside the same family, without an interposing relay.
Trip window stated on the release – the 0.35 to 0.7 Un band is written per family, because a release that holds at 60 percent of nominal is not protecting the load.
Short time coil that cuts itself off – the shunt trip contact opens after the trip, so the coil does not burn if the control signal stays on, which is why no timer is needed in the circuit.
Status contact versions – the iMX+OF and the ABB auxiliary blocks add one changeover contact, so the PLC sees the breaker position rather than assuming the command worked.
Fits the breaker it is ordered with – each row names the breaker families it mounts on, so a coil is not bought for the wrong frame width.
Applications
These three uses explain most orders, and each one sets a different requirement on the coil.
Emergency off and fire panel trip – a shunt trip driven by the emergency circuit or the fire panel, opening the incoming breaker without anyone reaching the panel door.
Guarded machine interlock – an undervoltage release held closed by the guard circuit, so the drive cannot be re-energised while the guard is open and the breaker drops if the circuit is broken.
Remote load disconnection – a PLC output through a shunt trip on a feeder that has to be shed at night, with the status contact returning the breaker position to the controller.
The trip circuit is quoted with the board that drives it, so the SUPERB PCBA and the SUPERB PCB are checked against the same panel list and the output contact rating agrees with the coil current.
Sourcing and Cross-Reference
Write the coil voltage down before the brand. A 230 V AC coil on a 24 V DC control rail is a dead part on arrival, and the mistake is easy to make because the same family is sold at four voltages with one character of difference in the code. If the panel has both rails, decide which one the trip circuit belongs to and keep it there.
Decide whether the circuit must fail safe. A shunt trip does nothing when the control supply is lost, so a machine that must open on power failure needs an undervoltage release, or the shunt trip has to sit on a circuit that is itself supervised. In an emergency off loop the release is usually the cheaper and clearer answer.
Check the continuous consumption on the release. An undervoltage release holds 2 to 4 VA per breaker for as long as the panel is live, and a row of twenty of them is a real load on a small control transformer. The same calculation decides the transformer size, so see the control transformers page, and lead time and availability when the type is on allocation.
The SUPERB Assembly team runs the release coil on its own pair back to the guard circuit, because a release sharing a terminal with a signal lamp is the usual reason a machine will not reset.
Q: Can you supply the trip coils already fitted to the breakers, so the panel arrives with the accessory in place?
A: Yes. Send the breaker family, the control voltage and whether the circuit has to fail safe, and the SUPERB Tech team returns the coil, the width and the status contact that fit.
Why Panel Builders Buy Trip Coils From SUPERB
- Function named per row: shunt trip and undervoltage release are never mixed in one list, because the safe state of the panel depends on which one is fitted.
- Coil voltage explicit: the voltage and the current type are written out, so a 230 V AC and a 230 V DC part are not confused at the order stage.
- Compatibility listed: each row names the breaker families it mounts on, which avoids a coil that fits the slot but not the frame width.
- Trip window given: the percent band of the release is stated, so it can be checked against the emergency off requirement before the order is placed.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Residual Current Devices for Panel Feeders, Motor Protection Circuit Breakers for Panel Feeders, Control Transformers for Panel Control Voltage, Phase Failure and Voltage Monitoring Relays, Surge Protective Devices for AC Distribution Boards.