Busbars and Earth Bars for Panel Power Distribution
Product Specifications
Product Overview
A busbar replaces a bundle of cable with a bar of copper. The current that would need a 240 mm cable is carried on a 100 x 10 mm bar, the connections are bolted rather than crimped, and the run can be tapped at any point along its length. That is why a panel with a 1600 A incomer is built from bars and a panel with a 63 A feeder is built from cable.
The system is a set of parts, not a single item. A support holds the bars, the bars are bolted to the support, spacers keep the phases apart, a claw holds the bar against the support, and covers close the live faces. A support that is missing, or a bar that is on the wrong pitch, changes the short circuit rating of the whole run.
The ratings are a system rating and they depend on the spacing. The 100 kA short circuit rating and the 1900 A current are quoted with supports at 450 mm centres and a 165 mm bar spacing. Spacing the supports further apart lowers the short circuit withstand, because the electromagnetic force between two bars during a fault grows with the distance between the supports.
Two levels cover a panel. A flat bar system carries the main incomer and the distribution bars, and a neutral or PEN rail carries the return current in a smaller section, usually 3 x 10 mm copper, mounted on insulators inside the cable compartment. Both are ordered by the part, and both need the torque value from the sheet rather than a guess from the fitter.
Key Specifications
| Parameter | Flat busbar system | Neutral and PEN rail |
|---|---|---|
| Bar size | Up to 4 bars of 100 x 10 mm per phase | 3 x 10 mm copper, 1000 mm long |
| Rated current | 1900 A with 4 x 100 x 10 mm bars | 140 A for the 3 x 10 mm rail |
| Short circuit rating | 100 kA at 600 V, 3 phase, with supports at 450 mm | Not a short circuit rated assembly |
| Voltage | 600 V, 3 phase AC | 400 V nominal in a terminal block assembly |
| Support spacing | 450 mm maximum | Rail mounted on insulators |
| Bar spacing | 165 mm between phases | Single rail |
| Connection torque | 20 Nm for the system screws, 9 to 12 Nm at the support | Per the terminal block on the rail |
| Material | Copper bar, steel support with insulating body | Copper, tin plated |
| Ambient | 40 C maximum | Inside the enclosure |
| Approvals | UL 508 and CSA C22.2 No. 14 assembly rating | IEC 60947-7-1 for the terminal blocks that fit it |
| Covers | Side, edge and end covers on separate part numbers | End brackets and covers |
| Mounting | Support bolted to the plate or the TS8 rail | Rail clipped to a DIN rail |
Included Models and Order Codes
The table is a bill of parts for one run. A support and a bar are two lines, and the spacers, the claw and the covers are three more. The busbar itself is supplied in 2400 mm lengths of 100 x 10 mm copper, and the supports are listed by the number of bars they can carry and the screw size they use, because the torque is fixed by the screw.
| Part Number | Item | Capacity or size | Connection | Torque or rating |
|---|---|---|---|---|
| 9676.002 | Busbar support, Flat-PLS 60 | Up to 4 x 60 x 10 mm | M8 screw | 8 Nm |
| 9676.004 | Busbar support, Flat-PLS 100 | Up to 4 x 100 x 10 mm | M10 screw | 9 Nm |
| 9676.020 | Support for stabiliser bar, 60 | Up to 4 x 60 x 10 mm | M8 screw | 10 Nm |
| 9676.021 | Support for stabiliser bar, 100 | Up to 4 x 100 x 10 mm | M10 screw | 12 Nm |
| 3590.015 | Copper busbar | 2400 x 100 x 10 mm | Drilled to the support | 1900 A in a 4 bar stack |
| 9676.641 | Longitudinal connector | Joins two bar lengths | M10 | 20 Nm |
| 9676.019 | Busbar claw | Holds the bar to the support | M10 | 20 Nm |
| 9676.024 | Busbar stabiliser | Bar system 100, single | Bolted | Mechanical |
| 9676.025 | Busbar stabiliser | Bar system 100, double | Bolted | Mechanical |
| 9676.027 | Busbar stabiliser | Bar system 100, triple | Bolted | Mechanical |
| 9676.503 | Spacer roll, 30 mm | Bar to bar, 30 mm | E-Cu | 550 A |
| 9676.504 | Spacer roll, 40 mm | Bar to bar, 40 mm | E-Cu | 1100 A |
| 9676.505 | Spacer roll, 50 mm | Bar to bar, 50 mm | E-Cu | 1800 A |
| 3083.000 | End cover | Closes the end of a bar stack | Snap on | Insulating |
| 3085.000 | Cover section, 1 m | Bars 40 x 10 to 60 x 10 mm | Snap on | Insulating |
| 3092.000 | Cover section, 1 m | Bar 30 x 10 mm | Snap on | Insulating |
Assembly Rules That Set the Rating
The numbers in the certificate are only valid if the assembly follows three rules: a support every 450 mm, at least one claw between two supports, and the stated torque on every screw. A run that is supported at 700 mm still conducts, and it no longer has the short circuit rating that was ordered.
| Rule | Value | Why it matters |
|---|---|---|
| Support spacing | 450 mm maximum | The electromagnetic force during a fault rises with the span between supports |
| Bar spacing | 165 mm between phases | The clearance and creepage distances are certified at this pitch |
| Claw between supports | At least one | Holds the bar down when the fault force pushes it sideways |
| System screw torque | 20 Nm | A loose joint is a hot joint, and heat is what starts a busbar fire |
| Support screw torque | 8 to 12 Nm depending on the support | The insulating body cracks above the stated value |
| Maximum ambient | 40 C | The 1900 A figure is quoted at 40 C, not at 60 C |
| Bar stack | 4 x 100 x 10 mm | Fewer bars reduce the current and the short circuit withstand |
| Neutral rail section | 3 x 10 mm, 1000 mm long | The rail carries the return current of the feeders, not the full incomer |
Key Features
System rating, not a part rating – 1900 A and 100 kA belong to the assembly with supports at 450 mm and a 165 mm pitch, and the rules are written down.
Supports for 60 mm and 100 mm bars – Two support sizes cover a four bar stack in either width, with M8 or M10 screws and a stated torque.
Bar in 2400 mm lengths – 100 x 10 mm copper in a length that reaches across a 2000 mm enclosure with the ends turned in.
Spacers that carry current – The 30, 40 and 50 mm spacer rolls are rated 550 A, 1100 A and 1800 A for a copper to copper joint.
Covers as separate lines – Side, edge and end covers close the live faces, and they are ordered by bar width so a 60 mm cover does not go on an 80 mm bar.
Stabiliser supports – A stabiliser bar holds the stack against a fault force on a long run, and the support for it is a different part number.
Neutral and PEN rail – A 3 x 10 mm tin plated copper rail at 140 A for the return current, mounted inside the cable compartment.
Traceable torque – The torque for the system screw, the support and the claw is on the sheet, so the panel is signed off against a number.
Applications
A busbar run is used where the current is too high for cable or where taps are needed along the length. The four cases below are the common ones.
Main incomer and distribution – A 1600 A incomer lands on a four bar stack, and the feeder bars are tapped from it at the positions on the panel drawing.
Energy storage and UPS panels – A battery string at 400 V is connected on bars rather than cable, because the taps and the disconnector are bolted to the bar.
Motor control centres – A vertical bar run feeds several starters, and the claw and the spacers hold the stack against the fault force of the largest starter.
Earth and neutral distribution – A 3 x 10 mm rail carries the return current in the cable compartment, and the terminal blocks that fit it are ordered with the rail.
A busbar run is laid out on the panel drawing with the support positions and the tap points marked, and the SUPERB PCB drawing carries the 450 mm spacing so the shop cannot drift. On the SUPERB PCBA build the bars are cut and drilled to the drawing before the panel is wired, because a bar that is drilled on the bench leaves swarf in a live compartment.
Sourcing and Cross-Reference
A busbar order is a bill of parts, and a missing part is a run that cannot be assembled. The support, the bar, the claw, the spacer, the end cover and the side cover are six lines, and the torque values for four of them are different. A quote that lists only the bar and the support is not a quote for a run.
The current rating is not a property of the copper alone. It depends on the number of bars, the ambient, the spacing and the way the bars are mounted. The 1900 A figure is for four 100 x 10 mm bars at 40 C in a certified assembly, and a single bar in the same enclosure carries a fraction of that.
The short circuit rating is the number that is hardest to keep. It is certified with supports at 450 mm and a claw between them, and a panel that is built with a wider span on the bench has lost the rating before it leaves the shop. The assembly rules are part of the order, not an afterthought.
SUPERB Assembly sets the supports at 450 mm, fits a claw between them, torques the system screws to 20 Nm and records the values on the panel checklist, because a joint that is finger tight heats up at half load.
Q: Can you quote a four bar Flat-PLS 100 run with 2400 mm bars, supports at 450 mm, the claws, the spacers and the side covers, for a 1600 A incomer at 400 V?
A: Send the current, the voltage, the number of bars, the panel height and the fault level. The SUPERB Tech desk replies with the support, the bar, the spacer, the claw and the covers, and states the support spacing that keeps the short circuit rating.
Why Buy Busbar Systems Through SUPERB
- Bill of parts, not just bars: Supports, claws, spacers and covers are quoted as one run, so the assembly is complete when it reaches the panel.
- Rating tied to the spacing: The 1900 A and 100 kA figures are quoted with the support spacing and the bar pitch that make them valid.
- Torque on the sheet: Every screw has a value, and the values differ between the system screw, the support and the claw.
- Neutral rail on the same order: The 3 x 10 mm tin plated rail and the terminal blocks that fit it are added to the same delivery.
- Panel build support: The assembly team mounts the supports at 450 mm, torques the joints and records the values, because an untorqued busbar is a hot joint waiting for load.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Grounding Studs and Earth Terminals for Chassis Wiring, Screw Terminal Blocks and Pluggable Connectors, Wire Ferrules and Crimp Sleeves for Terminal Blocks, Current Transformers and AC Current Sensing, One Stop BOM Sourcing, Power Management Cross Reference.