Direct-On-Line Motor Starters for Small Drives
Product Specifications
Product Overview
A direct-on-line starter is the cheapest way to start a cage motor: the contactor connects the winding straight to the line, the motor draws roughly six times its rated current for a few seconds, and the overload relay watches the current afterwards. Nothing is reduced and nothing is controlled, which is why the method suits pumps, fans, conveyors and small compressors where the supply can take the inrush.
The part that is usually misunderstood is the division of labour. The contactor switches, and it protects nothing. The thermal overload relay protects the motor against a sustained overload, and it is ordered separately on the enclosed TeSys LE range, which is stated in the data sheet and not always read. A starter without the relay is a switch with a pushbutton, and the first locked rotor will end the motor.
The setting on the relay is the motor full load current from its nameplate, not the starter rating and not the cable size. A 7.5 kW 400 V motor draws about 15.5 A, and that is where the dial goes, inside the range of the relay chosen. The same starter body will cover a band of motor sizes because the relay is interchangeable, which is also why the same enclosure can be ordered with a different relay for a different motor.
Key Specifications
| Family | Motor power at 400 V | Thermal current | Coil | Enclosure | Note |
|---|---|---|---|---|---|
| Schneider LE1D09 | 4 kW | 9 A | 220 V AC (M7) | IP65, IK07 | overload relay ordered separately |
| Schneider LE1D12 | 5.5 kW | 12 A | 220 V AC (M7) | IP65, IK07 | same 88 mm body as LE1D09 |
| Schneider LE1D18 | 7.5 kW | 18 A | 220 V AC (M7) | IP65, IK07 | 1.015 kg |
| Schneider LE1D25 | 11 kW | 25 A | 220 V AC (M7) | IP65, IK07 | 101 x 201 x 153.5 mm |
| Schneider LE1D35 | 15 kW | 35 A | 220 V AC (M7) | IP65, IK07 | sheet steel above 40 A |
| Siemens 3RA2110 | 0.09 to 4 kW | 0.14 to 4 A setting | 24 V DC or 230 V AC | open, S00 | breaker, contactor and link module |
| Siemens 3RA2120 | up to 7.5 kW | up to 16 A setting | 230 V AC | open, S0 | type 2 coordination at 150 kA |
Included Models and Order Codes
The code after the family is the frame and then the coil. On Schneider LE1D09M7 the 09 is the thermal current in amps and M7 is a 220 V AC coil; P7 is 230 V, N7 is 415 V, and the same starter is sold under each. On Siemens the 3RA2110 part number encodes the size, the setting range, the terminal type and the coil, so the setting range has to be read out of the code before the two units can be compared.
| Part number | Motor power at 400 V | Thermal current | Coil | Enclosure | Note |
|---|---|---|---|---|---|
| LE1D09M7 | 4 kW | 9 A | 220 V AC | IP65 | 0.92 kg, 88 x 166 x 128.5 mm |
| LE1D12M7 | 5.5 kW | 12 A | 220 V AC | IP65 | 0.92 kg |
| LE1D18M7 | 7.5 kW | 18 A | 220 V AC | IP65 | 1.015 kg |
| LE1D18N7 | 7.5 kW | 18 A | 415 V AC | IP65 | same body, 415 V coil |
| LE1D25M7 | 11 kW | 25 A | 220 V AC | IP65 | 1.015 kg |
| LE1D25P7 | 11 kW | 25 A | 230 V AC | IP65 | same body, 230 V coil |
| LE1D35M7 | 15 kW | 35 A | 220 V AC | IP65 | 4.32 kg |
| 3RA2110-0BH15-1BB4 | 0.06 kW | 0.14 to 0.2 A | 24 V DC | open, S00 | 3RV2011-0BA20 plus 3RT2015 |
| 3RA2110-0DS15-1BB4 | 0.09 kW | 0.22 to 0.32 A | 24 V DC | open, S00 | 3RV2011-0DA20 plus 3RT2015 |
| 3RA2110-0EE15-1BB4 | 0.09 kW | 0.28 to 0.4 A | 24 V DC | open, S00 | Iq 150 kA at 400 V |
Setting the Overload Relay From the Nameplate
The relay dial is set to the motor full load current, and the relay range has to contain that number. The table gives the usual 400 V figures so a starter and a relay can be chosen for a motor that is already on site.
| Motor rating at 400 V | Full load current | Starter frame | Relay range | Inrush at 6 times |
|---|---|---|---|---|
| 0.75 kW | 2.1 A | LE1D09 | 1.6 to 2.5 A | 12.6 A |
| 1.5 kW | 3.5 A | LE1D09 | 2.5 to 4 A | 21 A |
| 2.2 kW | 4.9 A | LE1D09 | 4 to 6 A | 29 A |
| 4 kW | 8.5 A | LE1D09 | 6 to 10 A | 51 A |
| 5.5 kW | 11.5 A | LE1D12 | 9 to 13 A | 69 A |
| 7.5 kW | 15.5 A | LE1D18 | 13 to 18 A | 93 A |
| 11 kW | 22 A | LE1D25 | 17 to 25 A | 132 A |
| 15 kW | 30 A | LE1D35 | 23 to 32 A | 180 A |
Key Features
Contactor and relay as one enclosure – the starter arrives with the pushbuttons, the contactor and the terminals in one IP65 box, so the machine builder mounts one part instead of three.
Overload relay interchangeable inside the range – the same body covers a band of motor sizes, which is why one spare enclosure can serve several machines if the relay is stocked separately.
Coil voltage codes that are readable – M7, P7 and N7 map to 220, 230 and 415 V AC, so a 415 V control circuit does not become a wrong order.
Type 2 coordination on the Siemens combination – the breaker and the contactor are matched so that a short circuit does not weld the contactor, which is the difference between a reset and a replacement.
IK07 impact rating on the plastic body – the enclosure survives a kick at a machine base, which is where an enclosed starter usually lives.
Manual and remote reset – the red button resets locally and the same contact can be wired to a remote reset, so a starter inside a guarded area does not need the door opened.
Applications
Direct-on-line is the right answer in three common cases, and each one sets a different requirement on the starter.
Pumps and fans on a stable supply – a starter sized to the motor full load current, with the overload set from the nameplate and a coil voltage taken from the control circuit.
Conveyors and small machine drives – an enclosed IP65 starter mounted at the machine rather than in the panel, so the operator can reset it without opening the cabinet.
Retrofit of an old contactor panel – the same starter replaces a contactor and a separate relay on a DIN rail, with the wiring and the overload setting carried over to one part number.
The starter is quoted with the machine harness that feeds it, so the SUPERB PCBA and the SUPERB PCB are checked against the same drawing and the coil circuit matches the control rail.
Sourcing and Cross-Reference
Ask for the motor nameplate, not the motor kW. Two motors of the same rating can differ by a few tenths of an amp, and the relay range that contains the higher figure is the one that has to be fitted. A starter chosen on kW alone will usually work and will occasionally nuisance trip in summer.
Decide the coil voltage from the panel. A 220 V AC coil on a 24 V DC control circuit is a common mismatch when a machine is copied from an older drawing, and the coil is not interchangeable inside the enclosure without opening it. The 415 V coil exists for panels that switch the control circuit at line voltage.
Plan the short circuit protection with the starter. A direct-on-line starter has no breaking capacity of its own, so the breaker or the fuses upstream are what interrupt a fault, and the coordination type decides whether the contactor survives. Related pages cover contactors, thermal overload relays and motor protection circuit breakers; lead time and availability covers the current position.
The SUPERB Assembly team sets the overload dial against the motor nameplate before the enclosure is closed and records the value on the label, because a starter that trips on a correct motor is usually a dial left at the shipping position.
Q: Can you supply the starter with the overload relay already fitted and set to our motor current?
A: Yes. Send the motor nameplate, the control voltage and whether the starter sits in the panel or on the machine, and the SUPERB Tech team returns the frame, the relay range and the enclosure.
Why Machine Builders Buy DOL Starters From SUPERB
- Motor power and current both listed: the kW and the thermal current sit in the same row, so the relay range can be checked without a second document.
- Coil code translated: the M7, P7 and N7 suffixes are written out as voltages, which removes the most common ordering error on this family.
- Relay as a separate line: the data sheet states that the overload relay is ordered separately, so a starter is not quoted as if it were complete.
- Enclosure rating stated: IP65 and IK07 are listed with the dimensions, so the mounting position and the cable entry can be planned before delivery.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Contactors and Reversing Contactors for Motor Loads, Thermal Overload Relays for Motor Protection, Motor Protection Circuit Breakers for Panel Feeders, Soft Starters for Motor Starting, Phase Failure and Voltage Monitoring Relays.