Capacitor Discharge Reactors and Discharge Modules
Product Specifications
Product Overview
A capacitor that has just been switched out still holds its charge. Before the step is closed again, the voltage at its terminals has to fall below 50 V, which is the condition in the standard and the condition a contactor or a thyristor module assumes. Fixed resistors across the terminals do that job, but they conduct all the time: on a 100 kvar bank they leave tens of watts in the enclosure, warm the capacitor terminals and age with every discharge.
A discharge reactor replaces that permanent load with a lossy inductor that carries the discharge current and very little else. The winding is arranged in a V across the phases, so the discharge path closes through the reactor rather than through the network, and the loss in normal operation stays under 1.6 W. The same unit shortens the wait: a step that needed three minutes with fixed resistors is below 50 V in under twenty seconds at 400 to 525 V, which is what makes fast reclosing possible at all.
The number that has to match is the discharge time against the controller delay. A controller set to a 10 s delay with a 50 kvar step at 400 V needs a discharge path that reaches 50 V inside 10 s, and the published tables give the time per kvar and per voltage. Where the delay is shorter than the table allows, the step is closed on a residual voltage, and the next inrush is larger than the first one.
Key Specifications
| Parameter | Value | Note |
|---|---|---|
| Function | discharge a capacitor step below 50 V between switchings | replaces fixed discharge resistors |
| Rated voltage | 230 to 690 V AC, three phase | 110 to 690 V on the ELECTRONICON unit |
| Capacitor range | 5 to 100 kvar per unit | two units where the step is built from two capacitor cans |
| Resistance | 7.5 kOhm on the TDK unit, 4.9 kOhm per coil on the ELECTRONICON unit, 6 kOhm on the BTB unit | resistance sets the discharge time |
| Discharge time at 400 to 525 V | below 5 s for 25 kvar, below 10 s for 50 kvar, below 20 s for 100 kvar | TDK published table |
| Discharge time at 525 to 690 V | below 3 s for 25 kvar, below 6 s for 50 kvar, below 12 s for 100 kvar | higher voltage, same kvar, shorter time |
| Discharge time at 230 V | below 10 s for 25 kvar, below 20 s for 50 kvar, below 40 s for 100 kvar | lowest voltage, longest time |
| Power loss in service | below 1.6 W | below 1 W on the ELECTRONICON unit |
| Free wheeling current | below 3.4 mA | the reactor is not a load in normal operation |
| Discharge frequency | one discharge per minute at 100 kvar | two units where the controller switches faster |
| Mounting | 35 mm DIN rail, clip on | mounted behind the contactor or the module |
| Degree of protection | IP20 to IP40 depending on the type | inside the enclosure |
| Terminals | 2 x 0.75 to 2 x 2.5 mm squared | 0.5 Nm fixing torque |
| Ambient temperature | -25 to +55 C | natural cooling |
| Weight and size | 0.5 kg, 90 x 46 x 66 mm on the TDK unit | fits the depth of a standard capacitor cubicle |
Included Models and Order Codes
The three families below do the same job with different winding arrangements, and the resistance in the row is what sets the discharge time. The TDK unit is a 7.5 kOhm reactor in a shockproof housing with a published table per kvar and per voltage. The ELECTRONICON unit uses two 4.9 kOhm coils in a V arrangement and is mounted directly on the capacitor terminal on the L and M versions. The BTB unit is a 6 kOhm resistor based module with the same rail mounting. Where the step is larger than 100 kvar, the maker tables use two units, and the row notes it rather than scaling the time.
| Type | Resistance | Voltage | Step range and mounting |
|---|---|---|---|
| TDK B44066E9900L001 | 7.5 kOhm, two windings in V | 230 to 690 V AC | 5 to 100 kvar, 35 mm rail, 0.5 kg |
| ELECTRONICON EL-DR | 4.9 kOhm per coil | 110 to 690 V AC | 5 to 100 kvar, rail or capacitor terminal |
| ELECTRONICON EL-DR L and M | 4.9 kOhm per coil | 230 to 600 V AC | 5 to 50 kvar, mounted on the capacitor terminal |
| BTB BRHDC | 6 kOhm | 230 to 690 V AC | 5 to 100 kvar, 35 mm rail, 110 x 50 x 75 mm |
| Gruparge discharge reactor | not published | 180 to 660 V AC | 12.5 kvar below 1.2 s, 50 kvar below 5 s, two units above 50 kvar |
Capacitance and Stored Energy per kvar
The discharge time follows from the capacitance, and the capacitance per kvar falls as the voltage rises. The table gives the delta connected capacitance of one kvar at four voltages and the energy still stored at 50 V, calculated as one half of capacitance times voltage squared. At 400 V a step that is discharged to 50 V still holds 1.56 percent of its energy, which is the reason the 50 V limit is a safety limit rather than a guarantee of an empty capacitor.
| Network voltage | Capacitance per kvar | Capacitance of 25 kvar | Energy left at 50 V |
|---|---|---|---|
| 400 V | 248.7 uF | 6.2 mF | 1.56 percent of rated energy |
| 440 V | 205.5 uF | 5.1 mF | 1.29 percent of rated energy |
| 525 V | 144.4 uF | 3.6 mF | 0.91 percent of rated energy |
| 690 V | 83.6 uF | 2.1 mF | 0.53 percent of rated energy |
Key Features
Discharge in seconds, not minutes – a 50 kvar step at 400 to 525 V is below 50 V in under 10 s, which is what allows a controller delay of 10 s to be used at all.
Loss under 1.6 W – the reactor carries the discharge current and almost nothing in service, so the enclosure does not gain the watts that fixed resistors leave behind.
Published time per kvar and voltage – the table separates 230 V, 400 to 525 V and 525 to 690 V, because the same step discharges three times faster at 690 V than at 230 V.
Rail mounting behind the switch – the housing clips onto a 35 mm rail in the space behind the contactor or the module, which a retrofit cubicle usually has.
One unit per step – the step is the unit of selection, and a step built from two capacitor cans takes two reactors rather than one larger unit.
Terminal and torque stated – 0.75 to 2.5 mm squared conductors at 0.5 Nm, which is the detail that decides whether the unit survives the first discharge.
Works with contactor and thyristor steps – the same reactor serves a contactor switched bank and a thyristor switched bank, and the discharge condition is identical for both.
Applications
Three duties where the discharge path, rather than the capacitor, sets the switching rate.
Fast switching banks on welding lines – the controller wants a step every few seconds, and the discharge reactor is the only part that makes that possible without closing on a charged capacitor.
Banks with a short controller delay – a delay set to 5 or 10 s assumes a discharge path that reaches 50 V inside it, and the reactor is what makes the setting honest.
Panels where heat is the limit – a closed cubicle with a 300 kvar bank cannot afford the watts of a resistor bank, and the reactor removes most of that loss.
On a bank that is assembled on a board, the SUPERB PCBA and the SUPERB PCB are checked against the same step list, so the discharge path is wired the same way on every step.
Sourcing and Cross-Reference
A discharge reactor is a small part that stops a whole bank, so the replacement is usually urgent. The check is the step kvar and the network voltage, then the controller delay: a unit that reaches 50 V in 20 s is no use on a bank set to a 10 s delay, even where the kvar matches. The second check is the mounting, because the ELECTRONICON L and M versions sit on the capacitor terminal and the rail mounted units do not fit that space.
The third check is the state of the capacitor. A step that stays above 50 V after the published time usually has a capacitor with reduced capacitance or an open internal fuse, and a new reactor will not fix it. Measuring the residual voltage at the terminals after the published time is the quickest way to separate the two cases.
For a bank waiting on one unit, the options are the same kvar from another family, two smaller units where the step is above 100 kvar, or the rail mounted version where the terminal mounted one is out of stock. See lead time and availability for a specific type.
The SUPERB Assembly team torques the reactor terminals to 0.5 Nm and leaves the discharge time on the step label, because a loose terminal on a discharge path is a hot joint at the second switching.
Q: Can you confirm the discharge time for our step kvar at our network voltage before we order a reactor for a bank with a short controller delay?
A: Yes. Send the step kvar, the network voltage and the controller delay, and the SUPERB Tech team returns the reactor type and the discharge time it meets.
Why Compensation Panels Take Discharge Reactors Through SUPERB
- Time table per voltage: the discharge time is quoted at 230 V, 400 to 525 V and 525 to 690 V, so a 690 V step is not given a 400 V figure.
- Loss stated: the under 1.6 W figure is on the page, which is the number a thermal calculation for a closed cubicle needs.
- Mounting separated: rail mounted and capacitor terminal mounted versions are listed as separate rows, because the space behind the switch is not the same as the space on the can.
- Discharge frequency stated: one discharge per minute at 100 kvar is written down, so a bank that switches faster is quoted two units instead of being told the reactor will cope.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Capacitor Switching Contactors for Power Factor Correction, Power Factor Correction Capacitors for Panel Compensation, Detuned Reactors and Harmonic Filters for Capacitor Banks, Reactive Power Controllers for Automatic Capacitor Banks, Thyristor Switches for Capacitor Bank Switching, Component Lead Time Solutions.