Static VAR Generators for Dynamic Reactive Compensation

A static VAR generator supplies or absorbs reactive current in steps smaller than a kvar, so the compensation follows the load instead of jumping between stages. Units run from 30 to 200 kvar at 400 V, with 480 V and 690 V families on the same frames. Full output is reached within 15 ms, and the target power factor runs from minus one to plus one. The unit is a converter, so it needs a current transformer, an air path and a short circuit protection, and all three decide whether it works.
quote now

Product Specifications

Product Overview

A capacitor bank resolves a load in steps. Between two steps the power factor sits somewhere below target, and a step that closes and reopens around the target is the hunting that a controller is tuned to avoid. A static VAR generator has no steps: it is a voltage source converter that injects reactive current in either direction, capacitive or inductive, in increments far below one kvar. The power factor stays at target because the compensation moves continuously rather than in jumps.

The same property makes it useful on a load that regenerates. A crane lowering a load, a press returning, or a drive braking pushes reactive power back into the network, and a capacitor bank cannot absorb it. A generator inverts the current direction and takes the surplus, which keeps the voltage at the point of connection steady. That is why the target range is written from minus one to plus one: the unit is expected to work on both sides of unity.

Sizing is on the reactive power that has to move, not on the transformer rating. A 630 kVA transformer feeding a load that swings by 200 kvar needs a 200 kvar unit, and the same transformer feeding a steady load at 0.9 power factor needs far less. The second number that has to be right is the current transformer: the unit measures through it, and a ratio entered wrongly makes the unit compensate the wrong quantity.

Key Specifications

ParameterValueNote
Rated capacity30, 50, 100 and 200 kvar at 400 V480 V and 690 V families on the same frames
Input voltage range228 to 456 V AC at 400 V nominal384 to 576 V at 480 V, 552 to 759 V at 690 V
Frequency50 or 60 Hz, 45 to 62 Hz rangeself sensing, no setting change
Converter topologythree level neutral point clampedlower switching loss and lower harmonic output than a two level bridge
Compensationstepless, capacitive and inductivetarget power factor from minus one to plus one
Response timebelow 15 ms to full outputthe unit follows a load change inside one mains cycle
Efficiency97 percent or betterabove 99 percent at half load on the large frames
Current transformer input150/5 to 30000/5ratio entered at commissioning, a wrong ratio compensates the wrong current
Parallel operationunlimited modules in parallelno derating for parallel units on the 400 V family
Coolingforced air, 115 to 500 litres per secondair path at the top and bottom of the enclosure
Noisebelow 56 dB on 30 and 50 kvar, below 65 dB on 100 kvar, below 75 dB on 200 kvarmeasured at one metre
CommunicationRS485 and Ethernet, Modbus RTU and Modbus TCPcentral panel for a group of modules
Display4.3 inch touch panel per module, 7 inch central panelvoltage, current, reactive power, temperature
Protectionover and under voltage, over current, short circuit, over temperature, inverter faultfault history of 500 events
Degree of protectionIP20other degrees on request
Ambient temperature-10 to +40 C without deratingderating up to +45 C
Altitude1500 m without derating1 percent per 100 m above, to 4000 m
StandardsCEinstallation per the maker manual

Included Models and Order Codes

The four 400 V modules share the control logic and differ in frame size, air flow and weight, which is what decides the cabinet. SVG 030 and 050 are rack or wall mounted units with a 4.3 inch panel and the same 115 and 222 litre per second air path. SVG 100 doubles the capacity in a deeper frame, and SVG 200 is the largest single module at 110 kg. Above 200 kvar the answer is parallel modules up to the capacity of the bus, and the large cabinet families from 480 kvar upward are built from the same modules.

TypeRated capacityAir flowFrame and weight
Sinexcel SVG 03030 kvar115 L per second500 x 515 x 180 mm rack, 23 kg
Sinexcel SVG 05050 kvar222 L per second500 x 546 x 190 mm rack, 28 kg
Sinexcel SVG 100100 kvar360 L per second500 x 605 x 269 mm rack, 44 kg
Sinexcel SVG 200200 kvar500 L per second500 x 722 x 370 mm rack, 110 kg
Sinexcel SVG 480480 to 2400 kvar in a cabinet5040 CFM smart coolingcabinet, 600 x 800 x 2200 mm and larger
Sinexcel SVG 600600 to 3000 kvar in a cabinet5040 CFM smart coolingcabinet, 600 x 800 x 2200 mm and larger
Sinexcel SVG 690690 to 3450 kvar in a cabinet5040 CFM smart coolingcabinet, 690 V network

Reactive Current per Capacity at 400 V

The cable and the protection are chosen on current, and the current of a reactive source is the capacity divided by the square root of three times the line voltage. The table gives that current for the four 400 V modules. A 200 kvar module draws 289 A at full output, which is why the busbar and the fuse in front of it are sized well above the 30 kvar case even though the control wiring is identical.

CapacityCurrent at 400 VCurrent at 480 VCurrent at 690 V
30 kvar43.3 A36.1 A25.1 A
50 kvar72.2 A60.1 A41.8 A
100 kvar144.3 A120.3 A83.7 A
200 kvar288.7 A240.6 A167.3 A

Key Features

Stepless output – the unit injects reactive current in increments far below a kvar, so the power factor stays at target instead of stepping around it.

Both directions – capacitive and inductive current come from the same converter, which is what a crane or a press with regenerative travel needs.

15 ms response – the loop closes inside one mains cycle, so a load that changes every cycle is followed rather than averaged.

Three level topology – the neutral point clamped bridge switches at a lower effective step, which keeps the output current clean without a large filter.

Parallel to any capacity – modules are paralleled on the bus, so a 600 kvar requirement is met with three 200 kvar units rather than one cabinet built around a single bridge.

Monitoring on the module – voltage, current, reactive power and temperature are on the module panel and on the bus, so a failing unit is visible before the power factor drops.

Current transformer range – 150/5 to 30000/5 covers a feeder as small as a single machine and as large as a main incomer.

Applications

Three networks where stepless compensation earns its cost against a stepped bank.

Cranes, hoists and port equipment – the load regenerates on the way down, and a unit that absorbs reactive power keeps the voltage steady where a capacitor bank would overcompensate.

Welding and resistance heating lines – the reactive demand changes within a cycle, and a stepped bank would switch continuously and wear out its contactors.

Weak grids at the end of a feeder – voltage support needs reactive current in both directions, and the 15 ms response holds the point of connection inside its window.

Where the unit shares a panel with controls, the SUPERB PCBA and the SUPERB PCB are reviewed against the same current transformer and the same metering point, so the two do not disagree about the power factor.

Sourcing and Cross-Reference

A generator replacement is a capacity and a voltage question at the same time. The frame carries a different capacity at 480 V and 690 V, and the capacity at the actual voltage is the number to compare. The second number is the air path: a 200 kvar module moves 500 litres per second, and a cabinet that housed a 50 kvar unit will not pass that air without a new top and bottom opening.

The third question is the current transformer. The unit compensates what it measures, and a ratio entered as 1000/5 when the core is 600/5 leaves the network under compensated at every load. Where a replacement unit is fitted to an existing core, the ratio has to be read from the core label rather than from the old unit settings.

For a site waiting on one module, the options are parallel modules to the same total, the next frame up with the surplus left as headroom, or a rental where the outage has a date. See lead time and availability for a specific frame.

The SUPERB Assembly team checks the current transformer ratio and the phase rotation at commissioning, because a generator with a reversed core compensates in the wrong direction.

Q: Can you confirm the capacity at our network voltage and the air path the module needs before we replace a unit in an existing cabinet?

A: Yes. Send the reactive power that has to move, the network voltage, the existing current transformer ratio and the cabinet space, and the SUPERB Tech team returns the frame that fits.

Why Power Quality Projects Source Static VAR Generators Through SUPERB

  1. Capacity per voltage: the 480 V and 690 V families are named with their own capacities, so a 690 V site is not quoted the 400 V kvar.
  2. Air path and frame given: air flow and dimensions sit on the row, because a module that fits the space but not the ventilation overheats in the first week.
  3. Current transformer range stated: the 150/5 to 30000/5 window is on the page, and the ratio is confirmed before shipment rather than after commissioning.
  4. Parallel path named: above 200 kvar the answer is parallel modules, and the capacity of the cabinet families is quoted so the total is reached in one step.

Related Product Families

This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Active Harmonic Filters for Low Voltage Networks, Power Factor Correction Capacitors for Panel Compensation, Thyristor Switches for Capacitor Bank Switching, Multifunction Power Meters and Power Quality Analyzers, Metering Current Transformers for Panel and Switchgear, Component Lead Time Solutions.