Wire Ferrules and Crimp Sleeves for Terminal Blocks
Product Specifications
Product Overview
A screw clamp closes on whatever is in it. If that is a bundle of stranded wire, the strands spread under the screw, some of them sit outside the clamp, and the joint resistance depends on how the screw happened to land. A ferrule fixes that by crimping the strands into a solid pin with a plastic collar that stops the strands at the clamp edge. The result is a joint that can be inspected, that does not need re-tightening to the same degree, and that can be removed and refitted without losing strands.
The ferrules on this page are the Phoenix AI range in the 8 mm contact length, with a 14 mm overall sleeve and an 11 mm stripping length. The parts are made from soft tin plated electrolytic copper with a polypropylene collar, are free of silicone and halogen, and correspond to DIN 46228-4 and UL 486F for size. The continuous temperature is 105 C with a 120 C short term, and the flammability rating is UL 94 HB.
The size sequence is worth reading as a table rather than as a part number. AI 0,5-8 WH is white, takes 0.5 mm2 or AWG 20, and has a 1.1 mm ferrule diameter with a 2.5 mm collar inside diameter. AI 0,75-8 GY is grey, 0.75 mm2 or AWG 18, with a 1.3 mm ferrule and a 2.8 mm collar. AI 1-8 RD is red at 1.0 mm2. AI 1,5-8 BK is black at 1.5 mm2 or AWG 16 with a 1.7 mm ferrule. AI 2,5-8 BU is blue at 2.5 mm2 or AWG 14 with a 2.3 mm ferrule and a 4.2 mm collar. The colour is the size code, which is why the same wire must not be fitted with two colours on one panel.
The collar diameter is the figure that gets checked last and matters most. A 2.5 mm2 ferrule with a 4.2 mm collar will not enter a terminal opening that is 3 mm across, and a 0.5 mm2 ferrule in a 4 mm2 terminal sits loose in the clamp. The ferrule diameter is the metal pin, the collar is the plastic shoulder, and both have to clear the terminal. On a spring clamp the collar is what the release tool pushes against, so a collar that is too short makes the terminal hard to open.
The twin ferrules are for the case where two conductors have to share one terminal. AI-TWIN 2 X 2,5-10 BU takes two 2.5 mm2 wires into a single 10 mm contact length, with an 18.5 mm overall sleeve and a 2.9 mm ferrule diameter, and the collar is a figure of eight that holds the pair side by side. It is the part to use where a loop is taken out of a terminal rather than doubled up under one screw, because two separate ferrules under one screw is what makes a clamp sit at an angle.
The practical points are crimp tool, strip length and pull test. The crimp is a four indent or a hexagonal profile, made with a tool matched to the ferrule size rather than to the wire, and the strip length has to match the contact length or the collar sits over bare copper. The pull test on the first unit is a few seconds and it catches the two failures that matter: a crimp that was made in the wrong die, and a ferrule that was the wrong size for the wire.
Key Specifications
| Parameter | Value | Applies to |
|---|---|---|
| Conductor range | 0.5 mm2 to 2.5 mm2 in single ferrules | AI series |
| AWG range | AWG 20 to AWG 14 | By size |
| Sleeve length | 14 mm | Single ferrules |
| Contact length | 8 mm | Single ferrules |
| Stripping length | 11 mm | Single ferrules |
| Ferrule diameter | 1.1 mm to 2.3 mm | By size |
| Sleeve wall | 0.15 mm | All sizes |
| Collar thickness | 0.25 mm to 0.30 mm | By size |
| Collar inside diameter | 2.5 mm to 4.2 mm | By size |
| Material | Electrolytic copper, tin plated, polypropylene collar | AI series |
| Standard | DIN 46228-4, UL 486F | AI series |
| Temperature | 105 C continuous, 120 C short term | AI series |
| Flammability | UL 94 HB | AI series |
| Twin ferrule | Two 2.5 mm2 in a 10 mm contact length | AI-TWIN 2 X 2,5-10 BU |
Included Models and Order Codes
The rows below are the 8 mm contact ferrules we quote most often. Conductor size, ferrule diameter and collar diameter are given per size, because the collar is what decides whether the ferrule enters the terminal.
| Part Number | Colour | Conductor | Sleeve Length | Contact | Ferrule Diameter | Collar ID |
|---|---|---|---|---|---|---|
| AI 0,5-8 WH | White | 0.5 mm2, AWG 20 | 14 mm | 8 mm | 1.1 mm | 2.5 mm |
| AI 0,75-8 GY | Grey | 0.75 mm2, AWG 18 | 14 mm | 8 mm | 1.3 mm | 2.8 mm |
| AI 1-8 RD | Red | 1.0 mm2, AWG 18 | 14 mm | 8 mm | - | - |
| AI 1,5-8 BK | Black | 1.5 mm2, AWG 16 | 14 mm | 8 mm | 1.7 mm | - |
| AI 2,5-8 BU | Blue | 2.5 mm2, AWG 14 | 14 mm | 8 mm | 2.3 mm | 4.2 mm |
| AI-TWIN 2 X 2,5-10 BU | Blue | 2 x 2.5 mm2 | 18.5 mm | 10 mm | 2.9 mm | 4.2 and 7.8 mm |
Key Features
Collar diameter stated – 2.5 mm to 4.2 mm collar sizes are listed, because the collar is what decides whether the ferrule enters the terminal opening.
Colour coded by size – White, grey, red, black and blue map to 0.5, 0.75, 1.0, 1.5 and 2.5 mm2, so a size is visible on the wire after crimping.
Contact length on the quote – The 8 mm contact and 11 mm strip length are given together, because a short strip leaves the collar over bare copper.
Twin ferrule for shared terminals – Two 2.5 mm2 conductors go into one 10 mm contact length, which is cleaner than two ferrules under one screw.
Standard and material – DIN 46228-4 and UL 486F are quoted with the tin plated copper body, because a terminal block approval is written against both.
Temperature rating – 105 C continuous and 120 C short term covers a cabinet and a machine frame without a second part number.
Applications
These parts are used on any stranded wire that lands in a screw clamp, a spring clamp or a pluggable terminal block.
Panel terminal blocks – An AI 1,5-8 BK ferrule on a 1.5 mm2 wire gives the clamp a 1.7 mm pin with a black collar, so the size is visible after the cover goes on.
Pluggable connectors – An AI 2,5-8 BU ferrule with a 4.2 mm collar seats in a 5.08 mm pluggable connector, and the collar stops the strands at the clamp edge.
Shared terminals – An AI-TWIN 2 X 2,5-10 BU ferrule takes two 2.5 mm2 conductors into one 10 mm contact, so a pair does not sit under one screw at an angle.
A ferrule is the last part on the wire and the first part in the terminal, so the sleeve length is checked against the SUPERB PCB terminal depth and the clamp opening before the harness drawing is issued. On the SUPERB PCBA route the ferrules are crimped after the wire is cut to length, because a ferrule crimped on a wire that is later shortened is a ferrule that gets cut off.
Sourcing and Cross-Reference
A ferrule is bought by conductor and by terminal. The conductor sets the ferrule diameter and the terminal sets the collar size, and a part is only right when both fit. When a ferrule is replaced on a panel that is already wired, the conductor cross section, the terminal series and the strip length are the three figures to send, because a 4.2 mm collar in a 3 mm opening is not going in.
The second point is the crimp. A ferrule crimped in the wrong die looks closed and pulls apart at 30 N, and the failure shows up as a hot terminal rather than as a loose wire. The tool is matched to the ferrule size, not to the wire, and the profile is a four indent or a hex. The strip length has to be the contact length, so the collar sits on the insulation rather than over bare copper, and the copper should be visible at the collar edge by about a millimetre.
The third point is the terminal itself. A spring clamp needs the collar to push against, a screw clamp needs the pin to sit under the clamp plate, and a pluggable connector needs the pin to reach the contact spring. The same ferrule can be right for one and wrong for the other. We quote the ferrule with its sleeve and contact length, because those two figures are what the terminal drawing is checked against.
SUPERB Assembly pulls the first crimped ferrule at the quoted force and checks the sleeve against the terminal collar, because a ferrule that is one size small goes into the clamp but leaves strands outside it.
Q: Can you supply insulated ferrules for 1.5 mm2 and 2.5 mm2 wire with an 8 mm contact length, and confirm the collar diameter for a 5.08 mm pluggable connector?
A: Send the conductor cross section, the terminal series and the stripping length. The SUPERB Tech desk quotes the ferrule with its sleeve length and its ferrule diameter, because a 2.5 mm2 ferrule needs a 4.2 mm collar and will not enter a 2.5 mm terminal opening.
Why Buy Wire Ferrules Through SUPERB
- Conductor and terminal checked together: The ferrule diameter and the collar diameter are quoted as a pair, which is where a 4.2 mm collar gets ordered for a 3 mm opening.
- Colour code on the wire: The size colours are on the page, so a 2.5 mm2 wire is not fitted with a 1.5 mm2 ferrule and found at inspection.
- Strip length stated: The 11 mm strip and 8 mm contact are given together, because the collar has to land on insulation rather than on copper.
- Twin version available: Two conductors into one terminal is quoted as a single part, which keeps the clamp square.
- Pulled at assembly: The first crimp is pull tested, because a ferrule crimped in the wrong die looks closed and fails at the terminal.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Screw Terminal Blocks and Pluggable Connectors for Field Wiring, Wire to Board Crimp Housings and Headers for Harness Builds, Heat Shrink Tubing and Sleeves for Harness Protection, Cable Markers and Wire Labels for Harness Identification, Turret Terminals and Solder Lugs for Panel Wiring, How to Verify a Drop in Replacement.