Lockout Hasps and Safety Tags for Maintenance
Product Specifications
Product Overview
Lockout is a mechanical argument: the device has to hold the isolation point in the off position while every person working on the machine has their own lock on it. A hasp is the part that turns one point into many, and the number of holes decides how many people can work under one isolation.
The hasp is chosen by the isolation point, not by the padlock. A 25 mm jaw fits a small breaker handle and a 38 mm jaw fits a larger one; a 12 or 24 hole aluminium hasp is for a group lockout on a single switch, while the snap-on 427 is for a handle that cannot be reached from behind. Steel and aluminium bodies take the abuse; the nylon 428 is for electrical work where a metal body is not wanted.
Padlocks and tags complete the set. A 4.76 mm stainless shackle fits the smaller hasp holes and resists weather; a 6 mm plated shackle is the heavier option. The tag carries the name, the reason and the date, and its pull strength matters because a tag that tears off leaves the lock without an owner.
Key Specifications
| Hasp type | Inside jaw | Padlock capacity | Body material | Typical use |
|---|---|---|---|---|
| Steel hasp | 25 mm | 6 | Steel with vinyl handle | Breaker handles and small switches |
| Steel hasp, wide | 38 mm | 6 | Steel with vinyl handle | Larger handles and disconnect levers |
| Heavy duty steel | 25 mm | 4 | Powder coated steel | Outdoor and heavy duty isolation |
| Heavy duty steel, long | 76 mm | 8 | Powder coated steel | Long levers and gate arms |
| Aluminium hasp | 25 mm or 38 mm | 6 | Aluminium | Corrosion resistance, light weight |
| Nylon hasp | 25 x 63 mm | 6 | Nylon | Electrical work, non-conductive |
| Snap-on hasp | 44 x 54 mm | 5 | Aluminium | Handle that cannot be reached from behind |
| Dual jaw hasp | 44 x 54 mm | 8 | Aluminium | Two isolation points on one tag |
| Stainless hasp | 25 mm | 8 | Stainless steel | Wash down and chemical areas |
| Group hasp, 12 hole | 27 mm | 12 | Aluminium | Crew lockout on one switch |
| Group hasp, 24 hole | 27 mm | 24 | Aluminium | Large crew or contractor lockout |
Included Models and Order Codes
Part numbers below are the Master Lock safety range. The jaw size is the inside clearance, so a 25 mm hasp goes over a handle of 25 mm or less, not over a 25 mm padlock.
| Part number | Type | Jaw or opening | Padlock capacity | Notes |
|---|---|---|---|---|
| 416 | Aluminium hasp | 25 mm | 6 | Spark resistant |
| 417 | Aluminium hasp | 38 mm | 6 | Spark resistant |
| 418 | Heavy duty steel hasp | 25 mm | 4 | Powder coated |
| 419 | Heavy duty steel hasp | 76 mm | 8 | Long lever |
| 420 | Steel hasp, vinyl handle | 25 mm | 6 | Standard length |
| 421 | Steel hasp, vinyl handle | 38 mm | 6 | Wide jaw |
| 427 | Snap-on hasp | 44 x 54 mm | 5 | Write-on label, red or yellow |
| 428 | Nylon hasp | 25 x 63 mm | 6 | Non-conductive |
| 429 | Dual jaw aluminium hasp | 44 x 54 mm | 8 | Two jaws |
| S431 | Stainless steel hasp | 25 mm | 8 | 316 grade body |
| S440 | Aluminium group hasp | 27 mm | 12 | 12 holes |
| S450 | Aluminium group hasp | 27 mm | 24 | 24 holes |
Padlocks, Devices and Tags
The padlock is personal and the device belongs to the isolation point. The table keeps the two apart: a 4.76 mm shackle padlock will not pass through every breaker lockout, and a plug lockout has to be sized on the plug body, not on the cable.
| Part number | Type | Size or rating | Keying or capacity | Pack |
|---|---|---|---|---|
| S31 | Safety padlock, stainless shackle | 4.76 mm shackle, 38 or 76 mm clearance | Key retaining | 1 pc |
| S32 | Safety padlock, dielectric | 4.76 mm nylon shackle, 38 mm | Key retaining | 1 pc |
| S33 | Safety padlock, snap lock | 4.76 mm stainless shackle, 38 or 76 mm | Non key retaining | 1 pc |
| 410 | Safety padlock, plated shackle | 6 mm shackle, 38 or 76 mm | Key retaining | 1 pc |
| 406 | Safety padlock, non-sparking | 6 mm nylon shackle, 38 mm | Key retaining | 1 pc |
| 491B | Breaker lockout | Tall and wide toggles, 480 V | Accepts safety padlocks | 1 pc |
| 493B | Breaker lockout | Standard and tie-bar toggles, 120 to 240 V | Accepts safety padlocks | 1 pc |
| S3821 | Miniature breaker lockout | 120 to 240 V | Accepts safety padlocks | 1 pc |
| S3822 | Moulded case breaker lockout | 480 to 600 V | Accepts safety padlocks | 1 pc |
| S3823 | Oversized handle lockout | 480 to 600 V | Accepts safety padlocks | 1 pc |
| 487 | Plug lockout, small | Plug 57 x 83 mm, cord up to 19 mm, 110 to 240 V | Accepts hasps | 1 pc |
| 488 | Plug lockout, large | Plug 76 x 152 mm, cord up to 19 mm, 240 to 550 V | Accepts hasps | 1 pc |
| 480 | Gate valve lockout | Handle 25 to 76 mm, stem opening 19 mm | Accepts hasps | 1 pc |
| 481 | Gate valve lockout | Handle 51 to 127 mm, stem opening 38 mm | Accepts hasps | 1 pc |
| WKT3 | Do Not Operate tag, paper | 146 x 76 mm, 1 in ring | 25 tags | 25 pcs |
| 122984 | Do Not Operate tag, polyester | 146 x 76 mm, brass grommet, 34 kg pull | 10 tags | 10 pcs |
| 65520 | Do Not Operate tag, heavy duty | 146 x 76 mm, -40 to 80 C | 25 tags | 25 pcs |
Key Features
Capacity matches the crew – 4 to 24 padlock positions on one isolation point, so a contractor crew and the plant team can lock the same switch.
Jaw size by handle – 25 mm, 38 mm and 76 mm jaws cover breaker handles, disconnect levers and gate arms.
Body material by area – steel for general work, aluminium for spark risk, nylon for electrical work and stainless for wash down.
Padlock shackle by hasp – 4.76 mm stainless and 6 mm plated shackles, key retaining or snap lock for group work.
Device by isolation point – breaker, plug and gate valve devices are listed by the shape they clamp, not by catalogue family.
Tag pull strength stated – the polyester tags carry a 34 kg pull rating against a torn tag that leaves a lock unlabelled.
Applications
Lockout kits are built per machine, and the same three isolation points come up.
Automation and drive panels – breaker lockouts on the main and the drive feed, with a 25 mm hasp on each and a personal padlock per fitter.
Pump and valve stations – gate valve lockouts on the isolation valve, with a 24 hole group hasp where a crew of contractors is on site.
Test and laboratory benches – plug lockouts and prong lockouts for equipment that is moved between benches and has no fixed isolator.
A lockout kit is quoted against the isolation points on the drawing, and the SUPERB PCBA and the SUPERB PCB are checked against the same panel schedule so every breaker and valve has a device that fits.
Sourcing and Cross-Reference
Buy the device before the padlock. A breaker lockout has a fixed opening and only some padlock shackles pass through it, so a 6 mm shackle can turn out to be the wrong purchase after the device is on the toggle.
Match the tag to the environment: paper tags are for indoor cabinets, polyester for grease and water, and heavy duty laminate where the tag is handled every shift.
Keep the keying policy in one order: keyed alike sets for a crew, master keyed for the supervisor, and key retaining where a lock must never be left open. Mixed keying is the most common reason a lockout procedure fails an audit.
Isolation devices for older breakers are often obsolete. Obsolete part cross reference covers the current device for a toggle that is no longer listed.
The SUPERB Assembly team fits the breaker lockouts while the panel is still on the bench, because the device has to be tried on the toggle before the door goes on.
Q: Can you match a lockout device to a breaker that is already installed?
A: Yes. Send a photo of the breaker toggle or the valve handle with a ruler in frame; the SUPERB Tech team quotes the device that fits that shape.
Why Maintenance Teams Buy Lockout From SUPERB
- Device matched to the isolation point: the quote starts from the breaker or valve shape, not from a catalogue page.
- Hasps, locks and tags in one line: one order covers the mechanical device, the padlocks and the tags for the same isolation.
- Keying kept consistent: keyed alike, master keyed and key retaining sets are quoted as one policy.
- Replacement for obsolete devices: where the original breaker is out of production, the current device is matched to the toggle.
Related Product Families
This page is part of the component range we supply for industrial, telecom, medical and defence builds. Continue with: Cam Locks and Key Locking Latches, Draw Latches and Toggle Latches, Signal Towers and Stack Lights, Obsolete Part Cross Reference.